Technical Data | HPC-50K-TT | HPC-100K-TT | HPC-250K-TT |
DC Input | |||
Maximum Input Voltage | 850 V | ||
Voltage Range | 500~850 V | ||
AC Output (On-Grid) | |||
Rated Output Power | 50 kW | 100 kW | 250 kW |
Maximum Output Power | 55 kVA | 110 kVA | 275 kVA |
Maximum Output Current | 79 A | 159 A | 397 A |
Rated Grid Voltage | 400 V | ||
Rated Grid Frequency | 50/60 Hz (45~55 / 55~65) | ||
Power Factor (Rated Power) | >0.99 | ||
THDi (Rated Power) | <3% | ||
Power Factor | 1 (0.8 leading~0.8 lagging) | ||
Output System | 3PH, N, PE | ||
AC Output (Off-Grid) | |||
Rated Output Power | 50 kW | 100 kW | 250 kW |
Maximum Output Power | 55 kVA | 110 kVA | 275 kVA |
Overload Capacity | 110% Long Run | ||
Rated Output Voltage | 400 V | ||
Rated Output Frequency | 50/60 Hz | ||
THDu (Linear Load) | <3% | ||
Unbalanced Load Capacity | 100% | ||
General Data | |||
Maximum Efficiency | 96% | 97% | |
Protection | DC Overvoltage Protection, DC Short Circuit Protection, AC Overvoltage Protection, Polarity Reverse Protection, Module Temperature Protection | ||
Ingress Protection Rating | IP20 | ||
Isolation Transformer | Yes | ||
Temperature Range | -30~55ºC | ||
Cooling Method | Forced Air Cooling | ||
Relative Humidity | 0~95%, Non-condensing | ||
Altitude | ≤5000 m (>3000 m Derating) | ||
Display | Touch Screen | ||
Communication | Ethernet, RS485 | ||
BMS Communication | RS485, CAN | ||
Communication Protocol | Modbus, IEC104 | ||
Standby Consumption | <50 W | ||
Weight | 650 kg | 750 kg | 1600 kg |
Dimensions (WxDxH) | 1000x800x2015 mm | 1000x1050x2260 mm |
Commercial
PCS (Power Conversion System) (Built-in Transformer, 50kW / 100kW / 250kW)
- Power frequency topology, industrial design
- AC and DC dual power backup, ensure the power supply of the control system
- High power density, maximum efficiency up to 97%
- High-performance DSP, optimized control circuit design, better performance
- Wide DC input voltage range design, compatible with different batteries
- Functions of grid connected charging and discharging and off-grid independent inverter
- Reactive power and active power are adjustable
- Supports diesel generator access, seamless switching between on-grid and off-grid (optional)
- Cold start with load, three-phase 100% unbalanced load, strong load adaptability
- Friendly grid adaptability, accept power grid dispatch
- Intelligent management control strategy, multiple working modes, online or remote switching